![Daikin LCBKQ3AV1 Скачать руководство пользователя страница 298](http://html.mh-extra.com/html/daikin/lcbkq3av1/lcbkq3av1_service-manual_501887298.webp)
Troubleshooting
SiBE811001EB
297
CONVENI-PACK
[State]
[Malfunction]
[Retry]
[Irregular stop]
[Driving_permission]
[Defrost_control]
[Sensor]
[Data]
State 1
Normal display of 5 or 9
State 2
Normal display of 17
Error_code
According to
∗
1 on P.305
Error_detail
According to
∗
2 on P.306
INV_standby
INV. standby flag (0/1 (standby))
NON1_standby
STD1 standby flag (0/1 (standby))
NON2_standby
STD2 standby flag (0/1 (standby))
INV_Error_fixation
INV. error (0/1 (error fixed))
NON1_Error_fixation
STD1 error (0/1 (error fixed))
ON2_Error_fixation
STD2 error (0/1 (error fixed))
FAN1_Error_fixation
Outdoor unit fan 1 error (0/1 (error fixed))
FAN2_Error_fixation
Outdoor unit fan 2 error (0/1 (error fixed))
Bu
Booster operating permission (0/1)
Defrost_IN
During defrost IN (IN/OUT: 0/1)
Defrost_finish
Defrost completed flag (Finish: 1)
Defrost_end_on_the_way
Defrost finish mid-way (mid-way finish: 1)
HP_heat_mode_timer
Operation time in heating mode
HP_heat_gard
Guard timer for turning the four way valve B OFF
(0/1: Turning the four way valve OFF is prohibited)
Electric wiring diagram
Sh1
Suction SH
(refrigeration-side)
Ta
R1T
Outdoor air temperature
thermistor
Sh2
Suction SH
(air conditioning side)
Td1
R31T
Discharge thermistor
(INV)
Tdsh1
Discharge SH (INV)
Td2
R32T
Discharge thermistor
(STD1)
Tdsh2
Discharge SH (STD 1)
Td3
R33T
Discharge thermistor
(STD2)
Tdsh3
Discharge SH (STD 2)
Ti1
R21T
Suction pipe thermistor
(refrigeration-side)
TgSH
Intermediate SH
Ti2
R21T
Suction pipe thermistor
(air-conditioner-side)
Outdoor_SC
Outdoor subcooling
Tg
R4T
Plate type heat
exchanger outlet
thermistor
Te 1
Refrigeration-side
evaporating temperature
Tce
R6T
Outdoor unit heat
exchanger outlet
thermistor
Te 2
Air conditioning side
evaporating temperature
MP
S1NPH2
Intermediate pressure
sensor
Tcg
Condensing temperature
HP
S1NPH1
High pressure sensor
LPm
Target evaporating
temperature equivalent
pressure
LP1
S1NPL1
Low pressure sensor
(refrigeration-side)
LP2
S1NPL2
Low pressure sensor
(air conditioning side)