SiBE811001EB
Troubleshooting
CONVENI-PACK
296
8.6
Troubleshooting by RAM Monitor (Outdoor Unit)
Using the RAM monitor makes it possible to check the following operating data.
<Mode 1>
[MAIN]
[MODE]
SP_No
SP number
Ver.
Version of software
Operation_SW
Operating switch ON/OFF (OFF/ON:0/1)
Energy_saving_SW
Evaporating temperature shift contact point ON/OFF (OFF/ON:0/1)
LPSpoint_of_contact
STD1 compressor's low pressure protection LPS ON/OFF (OFF/ON:0/1)
A_low_tone_point_of_contact
Low sound contact point ON/OFF (OFF/ON:0/1)
Indoor_unit_driving
Indoor remote control ON/OFF (OFF/ON:0/1)
Outdoor_unit_driving
Outdoor operating condition (OFF/ON:0/1)
Thermostat_ON_ref_side_unit
Refrigeration-side thermostat ON conditions (Run/stop: 1/0)
Thermostat_ON_AC_side_unit
Air conditioning side thermostat ON conditions (Run/stop: 1/0)
Remote_controller_temperature_
control
Remote controlled temperature control (cooling:1; heating: 2; fan: 0)
Temperature_control_mode
Temperature control mode used during outdoor control (cooling: 2; heating: 1; fan: 0)
Mode
Displays operating mode (during cooling: 0 to 35; during heating: 40 to 80)
Next_mode
Next operating mode to be transitioned
Before_mode
Operating mode prior to current operating mode
Mode_complete
Flag for the completion of mode change-over (incomplete/complete:0/1)