Troubleshooting
SiBE811001EB
189
CONVENI-PACK
8.4.17 PCB Abnormality
Error Code
E1
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Abnormality is detected under the communication conditions in the hardware section between
the indoor unit and outdoor unit.
Error Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal.
Supposed
Causes
Defective outdoor unit PCB (A1P)
Defective connection of inside/ outside relay wires
Troubleshooting
External factor other than error
(for example, noise etc.).
YES
Connect the inside/ outside
relay wires correctly.
YES
Replace the outdoor unit main
PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Turn OFF the power once and turn
ON again.
Return to normal?
Check if inside / outside
relay wires of outdoor
unit main PCB is
disconnected.
NO