SiBE811001EB
Field Setting
CONVENI-PACK
122
These numbers represent the number of times to press the BS2 button to select each setting.
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
47
Heating capacity _ high pressure
correction
Purpose)
It uses it to adjust improvement/
down of the heating capacity.
Refer to details to another page.
k
h
h
k
k
k
k
48
Set temperature of H/P side start
when heating from mode 0 starts
and correction of inhalation
temperatures fluctuate
Purpose)
It uses it for the adjustment when
the heating capacity is started.
Refer to details to another page.
k
k
k
h
h
h
h
55
Standby timer on H/P side of
start of heating from mode 0
Purpose)
It uses it for the adjustment when
the heating capacity is started.
Refer to details to another page.
k
k
k
h
k
k
k
56
Setting of standby time of the
number of heat pump assistance
Purpose)
It uses it for the adjustment when
the heating capacity is started.
Refer to details to another page.
k
k
k
k
h
h
h
58
Heating capacity _ suction air
temperature correction 1
(minimum value of set
temperature and absorption
temperature degree difference)
Purpose)
It uses it to adjust improvement/
down of the heating capacity.
Refer to details to another page.
k
k
k
k
h
k
h
59
Heating capacity _ suction air
temperature correction 2
(maximum value of set
temperature and absorption
temperature degree difference)
Purpose)
It uses it to adjust improvement/
down of the heating capacity.
Refer to details to another page.
k
k
k
k
h
k
k
60
Heating capacity _ suction air
temperature correction 3
(fine-tuning of minimum value of
set temperature and absorption
temperature degree difference)
Purpose)
It uses it to adjust improvement/
down of the heating capacity.
Refer to details to another page.
k
k
k
k
k
h
h
Heating capacity_ high
pressure correction
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0MPa
k
h
h
h
h
h
k
Set 1
0.098MPa
k
h
h
h
h
k
h
Set 2
-0.098MPa
k
h
h
h
k
h
h
Correction temperature H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0°C
k
h
h
h
h
h
k
Set 1
-2°C
k
h
h
h
h
k
h
Set 2
-1°C
k
h
h
h
k
h
h
Set 3
1°C
k
h
h
k
h
h
h
Set 4
2°C
k
h
k
h
h
h
h
H/P side standby timer
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
120 sec
k
h
h
h
h
h
k
Set 1
30 sec
k
h
h
h
h
k
h
Set 2
25 sec
k
h
h
h
k
h
h
Mode 41 and 42
→
40
standby time
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
5 minutes
k
h
h
h
h
h
k
Set 1
7 minutes
k
h
h
h
h
k
h
Set 2
3 minutes
k
h
h
h
k
h
h
Heating capacity _ suction
air temperature correction 1 H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0°C
k
h
h
h
h
h
h
Set 1
1°C
k
h
h
h
h
h
k
Set 2
2°C
k
h
h
h
h
k
h
Set 3
3°C
k
h
h
h
h
k
k
Set 4
-1°C
k
h
h
h
k
h
h
Set 5
-2°C
k
h
h
h
k
h
k
Set 6
-3°C
k
h
h
h
k
k
h
Set 7
-10°C
k
h
h
h
k
k
k
Heating capacity _ suction
air temperature correction 2 H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0°C
k
h
h
h
h
h
h
Set 1
1°C
k
h
h
h
h
h
k
Set 2
2°C
k
h
h
h
h
k
h
Set 3
3°C
k
h
h
h
h
k
k
Set 4
-1°C
k
h
h
h
k
h
h
Set 5
-2°C
k
h
h
h
k
h
k
Set 6
-3°C
k
h
h
h
k
k
h
Set 7
-10°C
k
h
h
h
k
k
k
Heating capacity _ suction
air temperature correction 3 H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
1°C
k
h
h
h
h
h
h
Set 1
2°C
k
h
h
h
h
h
k
Set 2
3°C
k
h
h
h
h
k
h
Set 3
4°C
k
h
h
h
h
k
k
Set 4
5°C
k
h
h
h
k
h
h
Set 5
6°C
k
h
h
h
k
h
k
Set 6
7°C
k
h
h
h
k
k
h
Set 7
8°C
k
h
h
h
k
k
k
Set 8
9°C
k
h
h
k
h
h
h
Set 9
10°C
k
h
h
k
h
h
k
Set 10
11°C
k
h
h
k
h
k
h
Set 11
12°C
k
h
h
k
h
k
k
Set 12
13°C
k
h
h
k
k
h
h
Set 13
14°C
k
h
h
k
k
h
k
Set 14
15°C
k
h
h
k
k
k
h
Set 15
16°C
k
h
h
k
k
k
k