Outline of Functions (Outdoor unit)
CONVENI-PACK
90
(6) Discharge gas temperature control
Discharge gas
temperature control
STD compressor or INV.
compressor dropping down
• Td (Discharge gas temperature) includes
Td1(INV.), Td2(STD1) and Td3(STD2)
• Predicted Tp (Discharge port temperature)
includes Tp_1(INV.), Tp_2(STD1) and Tp_3(STD2)
• TdSH (Discharge gas SH) includes TdSH1(INV.),
TdSH2(STD1) and TdSH3(STD2)
• TpSH(Discharge port SH) includes TpSH1(INV.),
TpSH2(STD1) and TpSH3(STD2)
• TgSH is intermediate SH
TgSH = Tg – f(MP)
Tg: Plate type heat exchanger outlet thermistor
MP: Intermediate pressure sensor
f(MP): Intermediate pressure equivalent saturation
temperature calculated
f(HP): High pressure equivalent saturation
temperature calculated
Drooping control of
compressor discharge gas
Outdoor Y2E control
Intermediate Y2E inching control
Intermediate Y2E wet avoiding control
Intermediate Y2E overheat avoiding control
Intermediate Y2E MP & intermediate SH control
Intermediate Y2E
inching control
Outdoor Y1E cooler control
Refrigeration oil recovery control 4
Outdoor Y1E SH control
OR
<When starting>
<At Steady Time>
• Successful condition formation
of Td sudden increasing
• When Td
≥
115˚C continues for
more than 1 minute
• Make the Y2E opening
degree up/down
OR
• Td > 60˚C continues for consecutive 10 seconds or more
• Min(TdSH, TpSH) > 20˚C continues for consecutive 20
seconds or more
• 5 minutes have passed after startup
Intermediate
Y2E wet
avoiding control
Intermediate
Y2E overheat
avoiding control
Intermediate Y2E
MP & intermediate
SH control
Intermediate SH control
Appropriate MP control
• When operating with either one
of air-conditioning/refrigeration
• When operating with either one
of air conditioning/refrigeration
• Control at target intermediate SH = 10˚C
• Calculates target MP from values, LP1 and P2, to control
Controls at target Td = 100˚C
or target Tp = 110˚C
When the below
condition is released.
When the below
condition is released.
Subtract the Y2E
opening degree
OR
OR
OR
• Td > 60˚C
• Min(Td,Tp) – f(HP) > 20˚C
• Td – f(HP) > 20˚C
• Td > 60˚C
• MaxTp > 125˚C
• Td > Target Td (100˚C)
&
&
• When operating with both air
conditioning and refrigeration
• TgSH
≤
15˚C
&
&
• Both the refrigeration and air
conditioning are under operation
• When the MP exceeds the target MP
&
or
• Td < 60˚C
• Min(Td,Tp) – f(HP) < 10˚C
• Compressor under operation has
continued for more than 1 minute.
&
• Refer to the refrigeration oil recovery 4
• Control at target SH2 = 8˚C
• Decreases the current opening degree of Y1E when suddenly wet