Outline of Functions (Outdoor unit)
SiBE811001EB
93
CONVENI-PACK
(10) Indoor unit fan control (Only forced instructions from outdoor unit provided.)
During redundant refrigerant recovery 3 control. ··· All indoor units are instructed to set fan to
“H”. (All units with remote controller OFF, thermostat OFF, or thermostat ON.)
During defrosting. ··· All indoor units are instructed to set fan to “OFF”.
When unit is in heating mode except for partial Heat Recovery mode & HP > 2.84 MPa. ··· All
indoor units are instructed to set fan to “H”.
When continuous heating operation is 4 minutes or less & unit is in partial Heat Recovery
mode & (HP < 1.96 MPa or in defrosting operation). ··· All indoor units that have the
thermostat ON are instructed to set fan to “L”. (released when HP > 2.45 MPa.)
When thermostat has switched ON from partial heat recovery mode or from 100% Heat
Recovery mode & HP > 2.45 MPa. ··· All indoor units are instructed to set fan to “H”. (All
units with remote controller OFF, thermostat OFF, or thermostat ON.)