SiBE811001EB
Troubleshooting
CONVENI-PACK
172
8.4.5 Indoor Unit Fan Motor Overload / Overcurrent / Lock
Error Code
A6
Applicable
Models
FXMQ
Method of Error
Detection
Detects when the separate fan power supply is turned OFF.
Error Decision
Conditions
When the separate power supply for the indoor unit fan is not detected as being turned ON
during operation.
Supposed
Causes
Defective power supply for indoor unit fan motor
Clogging drain piping
Actuation of indoor unit fan protection device
Poor fan wiring contact.
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Is the power supply
for indoor unit fan
connected correctly?
Restart.
Operation is normal.
NO
YES
YES
NO
Connect correctly.
The indoor unit fan motor may
have experienced an
unscheduled stoppage due to
overload, overcurrent, or lock.
Replace the indoor unit PCB.