SiBE811001EB
Troubleshooting
CONVENI-PACK
168
Indoor Unit Fan Motor Abnormality
Error Code
A6
Applicable
Models
FXHQ
Method of Error
Detection
This error is detected if there is no revolutions detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor unit fan motor
Broken wires
Defective contact
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Are the X4A and
X27A connectors
securely connected?
Is the power of
approx. 12VDC
supplied between the
Pins1 and 3 when the
X27A is disconnected
and the power supply
turns ON?
NO
YES
YES
NO
Properly connect the
connectors.
(At this time, check for any
defective connector contact or
broken wires.)
Check the indoor unit fan motor
and the wiring circuits of the
motor.
Replace the indoor unit PCB.