Troubleshooting
SiBE811001EB
331
CONVENI-PACK
9.3
References
9.3.1 Comparison with Conventional Model
New model (A type)
Conventional model (D type)
Main
specification
Refrigerant
R-410A
R-407C
Capacity at
refrigeration
Refrigerating (kW)
(50/60 Hz)
21.8
16.5
Freezing (kW)
3.35
1.10
Installation area of outdoor unit (m²)
0.94
0.96
Mass (kg)
Outdoor: 370, Bu: 47
Outdoor: 330,
Bu: 28, Inv. Box: 80
Operation sound (dB)
Outdoor: 62, Bu: 49
Outdoor: 57.5, Bu: 42,
Inv. Box: 43
Maintainability
Outdoor unit
Maintenance valve, Dryer
bypass filter incorporated
Maintenance valve
incorporated
Booster
Maintenance valve
incorporated
Maintenance valve: onsite
piping
Installation
flexibility
Max. piping length of outdoor unit (m)
130
100
Difference in height of outdoor unit (m)
(outdoor unit above installation)
35
30
Difference in height of outdoor unit (m)
(outdoor unit below installation)
10
5
Max. piping length of booster unit (m)
30
5
Difference in height of booster unit (m)
(Booster unit above Installation)
10
3
Difference in height of booster unit (m)
(Booster unit below Installation)
0
0
Installation site of booster unit
Indoor/Outdoor
installation
(Bu/Inv. Box integrated)
Bu: Indoor/Outdoor installation
Inv. Box: Indoor use
(Bu/Inv. Box separated)
Pipes
Number of pipes
4-pipe type
3-pipe type
Gas pipe size
φ
25.4×2
φ
28.6×2
Liquid pipe size
φ
9.5×2
φ
15.9
Booster discharge pipe size
φ
9.5
φ
9.5
Booster suction pipe size
φ
15.9
φ
15.9
Booster liquid pipe size
φ
6.4×2
Thermal
insulation of
suction pipe
Air-conditioner (mm)
20
20
Refrigerator (mm)
30
30
Freezer (mm)
50
50
Thermal
insulation of
liquid pipe
Air-conditioner (mm)
10
10
Refrigerator (mm)
20
10
Freezer (mm)
30
10
Booster discharge (120°C)
10
10
Wiring
Outdoor unit
Power supply
3-phase 380 to 415V
3-phase 380 to 415V
Refrigerating operation output
Voltage signal
Voltage signal
Freezing operation output
Voltage signal
Alarm output
Voltage signal
(2ch: Backup and Abnormal
stop)
Non-voltage 'a' contact signal
(1ch: Abnormal stop)
Operation SW
Remote
Non-voltage ‘a’ contact signal
(signal)
Remote
Non-voltage 'a' contact signal
(power)
Booster unit
Power supply
1-phase 220 to 240V
3-phase 200V (with
transformer)
Freezing operation output
Voltage signal
Non-voltage 'a' contact signal
Freezing showcase
operation output
Non-voltage 'a' contact signal
(signal)
Non-voltage 'a' contact signal
(signal)
Alarm output
Non-voltage 'a' contact signal
(power)
Alarm output
Non-voltage 'a' contact signal
(signal)
Interface
D-III
Operation SW
Remote
Non-voltage 'a' contact signal
(signal)