SiBE811001EB
Troubleshooting
CONVENI-PACK
298
[Actuator]
[Retry_count]
[indoor_unit_EV]
Electric wiring diagram
52C
M1C
INV. compressor (ON/OFF:0/1)
52C1_[X5A]
M2C
STD 1 compressor (ON/OFF:0/1)
52C2_[X5B]
M3C
STD 2 compressor (ON/OFF:0/1)
20S1_[X9A]
Y1R
Four way valve A (ON/OFF:0/1)
20S2_[X8A]
Y2R
Four way valve B (ON/OFF:0/1)
20S3_[X10A] Y3R
Four way valve C (ON/OFF:0/1)
SV0_[X7A]
Y6S
Receiver gas vent solenoid valve (ON/OFF:0/1)
R1_[X14A]
Operating signal (ON/OFF:0/1)
SV1_[X15A]
Y1S
Subcooling control solenoid valve (ON/OFF:0/1)
EV1
Y1E
Main electronic expansion valve (pulse: 0 to 480 Pls)
EV2
Y2E
Injection expansion valve (pulse: 0 to 480 Pls)
EV3
Y3E
Oil return (INV) (pulse: 0 to 480 Pls)
EV4
Y4E
Oil return (STD 1) (pulse: 0 to 480 Pls)
EV5
Y5E
Oil return (STD 2) (pulse: 0 to 480 Pls)
Ftc
Frequency table value
InvHz
INV. frequency
FanSp
Fan table value
TotalHz
Total Hz (When STD 1 is 50 Hz: calculated as a converted INV. value at 166 Hz)
F1_DC
INV. discharge gas temperature retry count
F2_NON1
STD 1 discharge gas temperature retry count
F3_NON2
STD 2 discharge gas temperature retry count
F4_Hp
High pressure protection retry count
F5_Lp1
Refrigeration-side low pressure protection retry count
F5_Lp2
Air conditioning side low pressure protection retry count
F7_OC1
STD 1 OC retry count
F8_OC2
STD 2 OC retry count
F9_DCLock
INV._E5 (lock) retry count
F10_Start_failure
INV._L9 (start-up failure/position inconsistency) retry count
F11_DC
INV._L8 (overcurrent) retry count
F12_DC
INV._L5 (instantaneous overcurrent) retry count
F13_DC
INV._U2 (insufficient voltage) retry count
F14_DC
INV._L4 (fin temperature increase) retry count
F17_Power_supply_non-equilibrium
INV._P1 (voltage equilibrium) retry count
F21_Fan1
Fan1_E7 (lock) retry count
F22_Fan1_position_signal
Fan1_H7 (position signal error) retry count
F24_Fan2
Fan2_E7 (lock) retry count
F25_Fan2_position_signal
Fan2_H7 (position signal error) retry count
Indoor_unit_EV (real)
Indoor EV typical opening degree (0 to 2000 Pls)
Indoor_unit_EV_control_state
Displays the judgement of overload/freeze-up prevention control
Indoor_unit_prevention_of_freeze
Displays the freeze-up prevention control situation
Indoor_unit_Prevention_of_overload
Displays the overload control situation