Field Setting
CONVENI-PACK
134
7.3
Field Setting with the Booster Unit
(1) Setting by the switches
This unit has settings that can be made using the DIP switch and the BS button.
The power must be turned OFF when setting the DIP switch, but must be turned ON when using the BS button.
(2) Setting items by DIP switch on the outdoor unit main PCB
(3) Location of switches on PCB
(4) Setting [Compressor upper limit] and [Open phase power supply]
Compressor upper limit (A3P_DS1)
Open phase power supply (A2P_DS1)
Compressor upper limit is OFF.
(Upper limit steps = 22) (Factory setting)
Open phase power supply is OFF.
(Factory setting)
Compressor upper limit is ON.
(Upper limit steps = 16)
Open phase power supply is ON.
DIP switch setting
Target evaporating
temperature setting
Compressor upper limit
• When using this unit as a condensing unit, this switch sets the target evaporating temperature in
increments of 5˚C.
(Factory setting: -35˚C)
• This is an upper-limit cut-off applied to the compressor operating frequency. It allows the compressor
to run in low noise mode.
Caution!: Causes performance loss.
(Performance drops by about 25%. Operating noise lowers by about 3 dB.)
Open phase power supply
setting
• This unit can be used indoors or outdoors. This switch should be used particularly for outdoor use for
low refrigerating loads or long stop times.
Typical refrigerating load: 0.7 kW.
Caution!: The open phase power supply setting causes operating noise which may not be desirable for
indoor conditions.
(A3P)
C/BOX (right)
DIP switch (A2P)
ON
OFF
1
2
3
4
1
2
(A2P)
DIP switch (A3P)
BS button (See following page for settings assigned to the BS button)
• Target evaporating
temperature setting
• Open phase power supply setting
Note) Do not move knob 1.
• Compressor upper limit
ON
OFF
1
2
3 4
ON
OFF
1
2
ON
OFF
1
2
3 4
ON
OFF
1
2