SiBE811001EB
Outline of Functions (Outdoor unit)
CONVENI-PACK
84
<2-20: Set 3>
Forcibly conducts refrigerant recovery with four way valve-B when 30 minutes of partial Heat Recovery operation have
been accumulated.
(3)-4 Refrigeration oil recovery 1
Recovers refrigerator oil held up in the AC indoor unit heat exchanger at cooling.
(3)-5 Refrigeration oil recovery 4
Recovers refrigerator oil held up in the AC outdoor unit heat exchanger at heating.
(3)-6 Refrigeration oil recovery 7
Recovers refrigerator oil held up in the refrigeration evaporating heat exchanger
(3)-7 Oil recovery on refrigeration side according to an increase in circulation amount
• Opening degree of EV of all indoor units > 0 pls
• Tc - Max(R3T) > 2˚C continues for consecutive 20 minutes or more
• Tc-Min(R2T) < 5˚C continues for consecutive 2 minutes or more
• Condition formation of indoor liquid discharge continues for more than 3 minutes
• HP > 2.94MPa
• Operation mode = 74, 75, 80 more than 30 minutes have been accumulated
• Operation mode:
74, 75, 80
Redundant refrigerant
recovery 3 by four way valve B
Operation mode: 64, 65, 70
• HP < 2.94MPa
&
OR
&
OR
During normal operation
Returns the target SH of all
indoor units to original
During oil recovery 1
Instructs forced target SH =
3˚C to all indoor units
&
OR
• Operation mode: Cooling mode
• More than 2 hours after the accumulated AC thermostat ON
• Air conditioning Operation mode: Heating, Fan, OFF
• Oil recovery 1 continues for 5 minutes or more
During normal operation
Return outdoor Y1E opening
degree to its original position
During oil recovery 4
Opening degree of outdoor Y1E: 1.3 -
1.8 times the current opening degree
&
OR
• Operation mode: Outdoor evaporative mode
• More than 60 minutes after the accumulated AC thermostat ON
• Outdoor Y1E > 400 pls continues for consecutive 10 seconds or more
• SH2 < 3˚C continues for consecutive 1 minute or more
• Operation mode: Except outdoor evaporative mode
• Oil recovery 4 is more than 3 minutes
&
2.94MPa
2.989MPa
Heating mode
Cooling mode
C: (HP_Droop 2)
Freezing operation output signal: OFF
Freezing operation output signal: ON
• HP < C MPa
• LP1 > 0.196MPa
• 30 sec. have passed
&
OR
• HP > C MPa
• LP1 < 0.147MPa
• 60 sec. have passed
OR
Yes
Yes
No
No
During normal operation
Turn the operation output [R1
signal (P1 and P2)] to ON.
Condition formation of oil recovery 7 termination
During refrigeration oil recovery 7
• Toil1: Continuous operation time of compressor for refrigeration
(Operation mode: 8, 11, 12, 17, 24, 29, 30, 35, 43, 46, 47, 52, 59, 64, 65,
70, 74, 75, 80)
• Toil2: The accumulated operation time in the case of the INV. and STD1
compressors are used as a compressor for refrigeration
(Operation mode: 24, 29, 59, 64, 74)
• LP1: Low pressure for refrigeration
• Compressor frequency and operation mode keep inrush status during oil
recovery 7
Freezing operation
output signal :
Remains ON
Oil recovery
7 termination
• Operation mode: 8, 11, 12, 17, 24, 29, 30, 35,
43, 46, 47, 52, 59, 64, 65, 70, 74, 75, 80
• Toil1 > 40 minutes
• Toil2 > 0.5 × 40 minutes.
&
OR
Normal
running
Oil recovery on refrigeration
side according to an
increase in circulation
amount
(Increase the compressor
speed on the refrigeration side)
• HP < 2.89MPa
• LP1 > 0.392MPa
OR
• Oil recovery continuous time 10 minutes or more
• Oil recovery accumulated time 30 minutes or more
• When the cumulative operation time is 120 minutes (refrigeration side: INV. only)