SiBE811001EB
Troubleshooting
CONVENI-PACK
232
Troubleshooting
∗
1. Disconnect the connector once, then reconnect it and check that it is securely connected.
Properly connect the
connectors.
Are the connectors of the
outdoor unit main PCB, and
inverter PCB all securely
connected? (
∗
1)
Continue the operation.
(It is supposed that the error
results from causes such as
instantaneous power failure.)
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
Replace the INV. compressor
(M1C).
The INV. compressor
has insulation
resistance of not more
than 100k
Ω
.
YES
NO
Not the “
LC
” error. Check the
error code again.
The micro-computer
normal monitor (green) of
the outdoor unit main PCB
(A1P) is blinking.
NO
YES
Replace the compressor inverter
PCB (A4P).
Has the compressor
inverter PCB (A4P)
caused damage?
NO
YES
Replace the fan motor.
The fan motor has
insulation resistance of
not more than 1M
Ω
.
YES
NO
Replace it with a correct PCB.
Is the type of the inverter
PCB correct?
NO
YES
Replace the outdoor unit main
PCB (A1P).
The “
LC
” error reoccurs.
YES