Test Operation
SiBE811001EB
49
CONVENI-PACK
∗
1. Sensor kit is prohibited in principle (BRYQ140A7)
Because there are several concern points like product loss, the sensor kit should be prohibition in principle.
(e.g.)
AC operation might be stopped automatically when no people are detected during continuously operation. In case
of this, heating capacity of indoor unit cannot be used for heat recovery mode during winter season.
In the case of new indoor units, please refer to the values described on a page;
Public relations about new indoor units connection condition with conveni-pack..
1. Model connectable with conveni-pack
2. Amount of refrigerant filling
The amount of refrigeration of an air conditioning unit given in service manual of R410A conveni-pack SiBE811001_A
P.48 (C4) becomes the following.
3. Other limitation conditions
There is no change to other limitation conditions.
- The minimum air conditioning total capacity … 8HP
- The maximum air conditioning total capacity … 12HP
- The maximum indoor unit connection number : 6 or less
- Prohibition of individual driving and control with less than 4HP
- Install the indoor unit for air conditioning in the same space.
-Adjust the total amount of the refrigerant connected VRV indoor unit to
4.1kg or less.
(The limitation of option kits is not.)
HP
Model name
HP
Model name
HP
Model name
2HP
FXCQ50AVEB
4HP
FXHQ100AVEB
4HP
FXUQ100AVEB
2.5HP
FXCQ63AVEB
3.2HP
FXCQ80AVEB
5HP
FXCQ125AVEB
HP
Model name
Amount of refrigerant
2HP
FXCQ50AVEB
0.6kg/unit
2.5HP
FXCQ63AVEB
0.9kg/unit
3.2HP
FXCQ80AVEB
0.9kg/unit
5HP
FXCQ125AVEB
1.3kg/unit
4HP
FXHQ100AVEB
1.1kg/unit
4HP
FXUQ100AVEB
0.7kg/unit
For each unit