![Daikin LCBKQ3AV1 Скачать руководство пользователя страница 253](http://html.mh-extra.com/html/daikin/lcbkq3av1/lcbkq3av1_service-manual_501887253.webp)
SiBE811001EB
Troubleshooting
CONVENI-PACK
252
8.5.2 Earth Leakage
Error Code
E2
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Error is detected by the earth leakage detector
Error Decision
Conditions
When there is a earth leakage (breaker ON/OFF)
Within 10 seconds after the power is turned ON
When there is a earth leakage (leakage detector PCB)
10 seconds or more have passed after the power is turned ON
Supposed
Causes
Compressor (or the complete product) has defective insulation
Temporary liquid return or refrigerant slugging (Defective electronic expansion valve in
showcase, solenoid valve and Y1E)
Power failure during operation
Prolonged power shut down
Within 10 seconds after the power is turned ON
Troubleshooting
LED Indications
First digit
l h k h h l l
Second digit
l k h h h l h
More than 10
seconds passed
since power-ON
Shut OFF power.
Remove the compressor lead wire.
Defective insulation on
compressor
Defective insulation on
entire product
Reset the power with the
operation switch set to OFF.
NO
Replace the compressor.
NO
Replace the defective parts.
YES
It is likely that earth leakage
occurred due to temporary liquid
return or refrigerant slugging.
Earth leakage is possible in the
event of power failure during
operation or prolonged power
shutoff.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES