Troubleshooting
SiBE811001EB
213
CONVENI-PACK
8.4.34 Outdoor Unit Fan Motor Signal Abnormality
Error Code
H7
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Detection of abnormal signal from fan motor.
Error Decision
Conditions
In case of detection of abnormal signal at starting fan motor.
Supposed
Causes
Abnormal fan motor signal (circuit error)
Broken, short or disconnection connector of fan motor connection cable
Fan Inverter PCB error (A5P, A9P)