8.4.47 Inverter Radiation Fin Temperature Rise Sensor Abnormality
Error Code
P4
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Error Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
∗
Error is not decided while the unit operation is continued.
"
P4
" will be displayed by pressing the inspection button.
Supposed
Causes
Defective radiator fin temperature thermistor
Defective inverter PCB
Defective inverter compressor
Defective fan motor
Troubleshooting
Replace the inverter PCB.
Is the thermistor
resistance value normal?
Continue operation.
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Measure resistance value of the
radiation fin thermistor.
YES
Replace the compressor (M1C).
The INV. compressor's
insulation resistance is
not more than 100k
Ω
.
YES
NO
Replace the fan motor.
The fan motor's
insulation resistance is
not more than 1M
Ω
.
YES
NO
Replace the inverter PCB.
Does the error recur
when the power supply
turns ON?
YES