SiBE811001EB
Troubleshooting
CONVENI-PACK
204
8.4.25 Target Evaporating Temperature Setting Abnormality
Error Code
EE
Applicable
Models
LRYEQ16AY1
LCBKQ3AV1
Method of Error
Detection
The target evaporating temperature setting error by communication box (BRR9A1V1)
Error Decision
Conditions
The target evaporating temperature setting is -20 degree or less by communication box.
Supposed
Causes
The target evaporating temperature setting is -20 degree or less by communication box.
Troubleshooting
The target
evaporating
temperature setting of outdoor
unit by communication box
is -20˚C or less
The target evaporating
temperature setting of outdoor
unit is -20˚C or more.
Turn DS2-4 of main PCB (A1P)
OFF.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.