Outline of Functions (Outdoor unit)
SiBE811001EB
91
CONVENI-PACK
(7) Outdoor subcooling control
(8) Defrost control
(9) Oil return control and control of Y3E to Y5E
1) Control outline of Y2E and Y3E to Y5E (for oil return of compressor)
1. Control of Y2E
Priority Order
Protects compressor overheating under operation
Controlled MP > MAX (LP1, LP2)
Takes intermediate control of SH when wet. If still wet, adjust compressor discharge SH.
2. Control of Y3E to Y5E
Controls 40 minute timing with 8 divisions for oil returning. The oil return time will be approximately 5 minutes.
• Ensures Y3E to Y5E are operated to adjust the oil returning volume of each compressor and the
adjustment of the oil returning volume is conducted based on low pressure.
Regarding overheat protection
As for Y2E control is conducted with intermediate pressure or intermediate SH
As for Y3E - 5, control is conducted with target Td
Regarding wet protection
As for Y3E - 5, control is conducted with Td SH.
Make it Td SH > 20 or Td > 60
Outdoor subcooling control
Indoor liquid refrigerant discharge control
Normal outdoor condenser control
Refer to the redundant refrigerant recovery 3
Y1E: 0pls
SV1: OFF
• Operation mode: 5 to 35:
Y1E: 480pls
• Operation mode: 5 to 35:
HP > 1.96 to 2.352MPa:
Y1E: SV1: ON
• HP < 1.47MPa:
Y1E: SV1: OFF
Partial Heat Recovery control
• Operation mode: 74, 75, 80 & HP > 2.94MPa:
Y1E: SV1: ON
• Operation mode: 74, 75, 80 & HP
≤
2.94MPa and Y1E_PLS < 20pls:
Y1E: SV1: OFF
• Operation mode: 74, 75, 80 & HP
≤
2.94MPa and Y1E_PLS
≥
20pls
Target SC = 5˚C (Changeable by service mode, 2 - 13)
SV1: ON or OFF
Target SC
Set 2-13
OFF
(Factory setting)
Set 1
Set 2
5˚C
10˚C
8˚C
Outdoor SC=f(HP) – Tce
f(HP): High pressure equivalent saturation temperature
calculated
Tce: Outdoor unit heat exchanger outlet thermistor
OR
OR
&
&
OR
OR
Outdoor evaporative mode
40, 41, 42, 43, 46, 52, 59
• LP2 < 0.59MPa continues for cumulative (60 + DEF cumulative
timer correction) min. or more
• HP > 2.599MPa
• HP > 2.256MPa continues for
cumulative 3 + (3 - 43) min. or more
• HP > 1.519MPa continues for
cumulative 12 + (2 - 36) min. or more
• HP > 1.372MPa continues for
cumulative 17 + (2 - 36) min. or more
• Operation mode: 5, 6, 7, 8, 11, 12, 24,
29, 30, 35 continues for 10 consecutive
min. or more
• Operation mode: 74, 75, 80 continues
for 20 consecutive min. or more
• Operation mode: 64, 65, 70 & Ta > 5˚C
continues for 30 consecutive min. or
more
• When defrosted
• Defrost operation continues for 4 +
(3 - 43) consecutive min. or more
• Defrost operation continues for 20
consecutive min. or more
∗
Indoor unit flap is upward during
defrost operation (Ver.139 or
later)
• LP2 < 0.59MPa continues for cumulative (30 + DEF cumulative
timer correction) min. or more
• Defrost terminated prematurely
<Resetting condition of cumulative timer>
Defrost mode
• Operation mode: 74, 75, 80
or
• Operation mode: 6, 7, 8, 11, 12