Troubleshooting
SiBE811001EB
219
CONVENI-PACK
Troubleshooting
∗
1. Error pressure sensor
∗
2. Voltage measurement point
Refer to P.295.
Error code
Pressure sensor
Electric symbol
J1
Air conditioning low pressure sensor
S1NPL2 (sub PCB)
JC
Refrigeration low pressure sensor
S1NPL1 (main PCB)
1. Set the low pressure gauge upright.
2. Connect the checker for VRV to the
gauge.
Reset the operation, and then restart
the outdoor unit.
Replace the low pressure
sensor.
Are the characteristics
of the low pressure
sensor normal?
NO
Replace the outdoor unit main
PCB or sub PCB.
YES
Replace the low pressure
sensor.
Are the characteristics
of the low pressure
sensor normal? (Make
a comparison between
the voltage
characteristics (
∗
1)
and the gauge
pressure.)
NO
YES
Replace the outdoor unit main
PCB or sub PCB.
Is the PCB pressure
detection normal?
(Make a comparison
between the checker
pressure data and the
voltage characteristics
(
∗
2). )
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Measure voltage (DC) here
Outdoor unit PCB
X31A (Blue)
Red
Black
White
(1)
(2)
(3)
(4)
+5V
Micro-computer
A/D input
Lo
w pressure
sensor
Low pressure
sensor
connector
CHECK 14
CHECK 14