SiBE811001EB
Troubleshooting
CONVENI-PACK
200
Refer to P.292.
Refer to P.292.
Put the power supply ON to check the
following LED lamps.
1) HAP lamp on the compressor
inverter PCB (A4P)
2) HAP lamp on the fan inverter
PCB (A5P, A9P)
Replace the fan inverter PCB.
YES
Replace the corresponding fan
motor.
YES
Replace the corresponding fan
motor.
YES
Replace the corresponding fan
motor.
YES
Replace the corresponding fan
motor.
YES
Replace the fan inverter PCB.
YES
Replace the fan motor 2.
NO
NO
NO
NO
NO
NO
A
No continuity of fuse
(F1U) on the fan
inverter PCB.
Unable to rotate the
fan manually with
ease when removing
the connector of the
fan motor.
Resistance value
between the power
supply wire terminal of
fan motor and the motor
frame (metal) is 1M
Ω
and below.
The resistance value
between UVW
phases of fan motor
is out of balance, or
short circuit between
UVW phases.
The signal wire short
circuits between Vcc
and GND and between
UVW and GND.
HAP lamp for the
A5P or A9P does
not blink on the
condition that HAP
lamp for A4P is
blinking.
CHECK 11
Check fan motor connector
(power supply wire)
CHECK 12
Check fan motor connector
(signal wire)
CHECK 11
CHECK 12