SiBE811001EB
Troubleshooting
CONVENI-PACK
328
Note of several booster units connection
The prefab for freezing
Cooling unit
Cooling unit
The prefab for freezing
Cooling unit
Cooling unit
To a refrigeration showcase
From a refrigeration showcase
T1
T2
T1
T2
T1
T2
Be sure to separate no-voltage contacts used for freezing operation command.
: Booster discharge pipe
: Suction pipe
: Liquid pipe
: Wires for f
reezing operation command (Thermo. signal)
To a refrigeration showcase
From a refrigeration showcase
Booster unit
Booster unit
Outdoor unit
Booster unit
Booster unit
Outdoor unit
<Precaution for field wiring in case 2 booster units are operated with 1 relay for freezing operation command>
(Thermo. signal)
Freezing operation
command relay
(Thermo. signal)
If no-voltage contacts used for freezing operation command are taken from
a single contact, micro potential difference will be caused to disable the
normal operation of the booster units (i.e., the thermostat not to turn OFF).
Freezing operation
command relay
(Thermo. signal)
T1
T2