Troubleshooting
CONVENI-PACK
158
<Contents of abnormalities and retries>
k
: ON
h
: OFF
l
: Blink
Reference
Code
Contents of Error
Confirmation 1
Confirmation 2
Main content
Details
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H1P
H2P
H3P
H4P
H5P
H6P
H7P
J0
Intermediate Pressure Sensor
Failure
Defective S1NPH2 (
∗
1)
l h k h l l h l k h h h h h
J1
Defective low pressure sensor for
the air conditioning
Defective S1NPL2 (
∗
1)
l k h h h h l
J2
Current Sensor Error
l k h h h l h
J3
Defective discharge pipe
thermistor
Defective R31 to R33T (
∗
1)
l k h h h l l
J4
Defective suction pipe thermistor
(air conditioning)
Defective R22T (
∗
1)
l k h h l h h
J5
Defective suction pipe thermistor
(refrigeration)
Defective R21T (
∗
1)
l k h h l h l
J6
Defective outdoor unit heat
exchanger outlet thermistor
Defective R6T (
∗
1)
l k h h l l h
J9
Defective plate type heat
exchanger outlet thermistor
Defective R4T (
∗
1)
l k h l h h l
JA
Defective high pressure sensor
Defective S1NPH1 (
∗
1)
l k h l h l h
JC
Defective low pressure sensor
(refrigeration side)
Defective S1NPL1 (
∗
1)
l k h l l h h
L1
Defective inverter PCB
l h k h l l l l k h h h h l
L4
Defective inverter radiating fin
temperature rise
Excessive heating of the radiation
fin
l k h h l h h
L5
Momentary overcurrent of inverter
compressor
l k h h l h l
L8
Momentary overcurrent of inverter
compressor
l k h l h h h
L9
Inverter compressor starting
failure
l k h l h h l
LC
Defective transmission between
inverter and main PCB
l k h l l h h
P1
Inverter over-ripple protection
l h k l h h h l k h h h h l
P4
Defective inverter radiating fin
temperature rise sensor
l k h h l h h
PJ
Defective field setting after
replacing outdoor unit main PCB
or faulty combination of PCB
l k h l l h l
U1
Reverse phase, open phase
Reversed phase, open phase of T-
phase
l h k l h h l l k h h h h l
U2
Power supply insufficient or
instantaneous failure
Insufficient voltage on INV.
l k h h h l h
Open phase in INV. (T-phase)
Error charging of the main circuit
condenser
U4
Defective transmission between
indoor units and outdoor units
Defective indoor/outdoor
transmission
l k h h l h h
Defective the indoor system
U7
Defective transmission between
outdoor units
Defective transmission (between
the main and sub PCB)
l k h h l l l
U8
Defective transmission between
main and sub remote controllers
l k h l h h h
U9
Defective transmission between
indoor and outdoor units in the
same system
Error in other indoor units in the
system
l k h l h h l
UA
Improper combination of indoor
and outdoor units
Defective combination of outdoor
unit, indoor unit, and remote
controller
l k h l h l h
UF
System is not set yet
Defective wrong wiring check
l k h l l l l
UH
Defective system, refrigerant
system address undefined
Erroneous wire connection
l k h l h l l
∗
1: Either short circuit or open.
First digit
Second digit
Display of Error codes