SiBE811001EB
Troubleshooting
CONVENI-PACK
292
Check on Connector of Fan Motor (Power Supply Cable)
(1) Turn OFF the power supply.
Measure the resistance between phases of U,V,W at the motor side connectors (3-core
wire) to check that the values are balanced and there is no short circuiting, while connector
or relay connector is disconnected.
Measurement of Signal Wiring Connector
(1) Turn OFF the power supply.
(2) Measure the resistance between Vcc and each phase of U,V,W, and GND and each phase
at the motor side connectors (5-core wire) to check that the values are balanced within the
range of ± 20 %, while connector or relay connector is disconnected.
Furthermore, to use a multiple meter for measurement, connect the probe of negative pole
to Vcc and that of positive pole to GND.
CHECK 11
Red
U
Measure the resistance
values between phases
U,V,W.
White
Black
V
W
CHECK 12
5 Gray
GND
Measure the resistance
values between Vcc
and U,V,W, and GND
and U,V,W.
4 Pink
3 Orange
2 Blue
1 Yellow
Vcc
W
V
U