SiBE811001EB
Troubleshooting
CONVENI-PACK
202
Troubleshooting
∗
1. Make measurement of resistance between the connector pins, and then make sure the resistance falls in
the range of 40 to 50
Ω
.
External factor other than error
(for example, noise etc.).
YES
Ensure correct connection.
NO
Replace the electronic
expansion valve coil.
NO
Replace the outdoor unit PCB
(A1P or A2P).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Turn power supply OFF, and turn
power supply ON again.
Return to normal?
Check the electronic expansion valve
corresponding to the error code “
E9
” in
the monitor mode.
NO
YES
The connector of
outdoor unit PCB (A1P)
for electronic expansion
valve is connected.
The coil resistance of
electronic expansion
valve is normal. (
∗
1)
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
Judgement criteria
40~50
Ω