Outline of Functions (Outdoor unit)
SiBE811001EB
97
CONVENI-PACK
(21) Mode transition
The below flow chart shows a summary of mode transitions.
Mode 11
(INV.: refrigeration;
STD2: air conditioning)
Mode 8
(INV.: refrigeration;
STD1: air conditioning)
Mode 0 (Stop)
• Operation switch: By turning OFF, all mode transitions to Mode 0
• Mode 12 and 35 are backup modes. (These modes occasionally occur while INV. is on standby.)
c
Cooling (except backup mode)
• Operation SW: OFF
• Refrigeration low pressure drop
• Protection device operating
• Refrigeration forced OFF
Mode 30
(INV.: refrigeration)
Mode 7 (priority)
(STD1: air conditioning)
Mode 6
(STD2: air conditioning)
Mode 5
(STD1, 2: air conditioning)
Mode 29
(INV., STD1: refrigeration)
• Refrigeration ability
increase request
• Oil recovery
• Secure differential
pressure
• Air conditioning: OFF
• Air conditioning low
pressure drop
• Increase in high
pressure
• Dropping electric
current
• Refrigeration
ability decrease request
• Dropping refrigeration low pressure
• Increase in high pressure
• Dropping electric current
• Refrigeration ability
decrease request
• Air conditioning: ON
• Recovery of excessive
refrigerant
• Operation SW: ON
• Refrigeration ON
• Air conditioning: ON
• Recovery of excessive
refrigerant
• Air conditioning: OFF
• Air conditioning low
pressure drop
• Air conditioning: ON
• Recovery of excessive refrigerant
• Air conditioning:
OFF
• Low pressure drop
• Increase in high pressure
• Dropping electric current
• Air conditioning low pressure drop
• Air conditioning ability increase request
• Air conditioning ability decrease
request
• Increase in high pressure
• Dropping electric current
• Air conditioning low pressure drop
• Air conditioning ability decrease request
• Increase in high pressure
• Dropping electric current
• Air conditioning low pressure drop
• Refrigeration ability
increase request
• Refrigeration ability decrease
request
• Decline in refrigeration low pressure
• Increase in high pressure
• Dropping electric current
• Air conditioning
ability increase
request
• Air conditioning ability decrease
request
• Increase in high pressure
• Dropping electric current
• Air conditioning low pressure drop
• Refrigeration: OFF
• Decline in refrigeration low pressure
• Operation SW: ON
• Remote controller: Cool
• Air conditioning: ON
• Refrigeration ability
decrease request
• Air conditioning ability
increase request
• Operation SW: ON
• Remote controller: Cool/
ventilation
• Air conditioning: OFF
• Protection device
operating
• Air conditioning forced
OFF
• During forced cleaning
• Refrigeration: OFF
• Decline in refrigeration
low pressure
• Refrigeration: ON
• Refrigeration:
ON
• Refrigeration: OFF
• Decline in refrigeration
low pressure
• Refrigeration: ON
• Refrigeration
ability increase
request
• Air conditioning ability increase request
Mode 17
(INV.: refrigeration;
STD1, STD2:
air conditioning)
Mode 24
(INV., STD1: refrigeration;
STD2: air conditioning)
Mode 11
(INV.: refrigeration;
STD2: air conditioning)
Mode 8 (priority)
(INV.: refrigeration;
STD1: air conditioning)