Troubleshooting
CONVENI-PACK
242
8.4.53 Transmission Error between Outdoor Units
Error Code
U7
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
With the micro-computer, check whether there is transmission between the outdoor units.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Defective outdoor unit PCB
Improper connection of transmission wiring between outdoor unit main PCB and sub PCB
DIP switch 2-1 of sub PCB are ON.
Troubleshooting
Fix the outdoor units multi
connection transmission wiring
and reset power.
Is there any broken
wire or erroneous
wire connection in the
communication wiring
of multi outdoor unit
system?
NO
Turn DS2-1 of sub PCB (A2P)
OFF.
DS2-1 of sub PCB (A2P) is ON
YES
Wiring between inside - outside
(F1, F2) to outdoor unit main
PCB (A1P).
Wired between indoor -
outdoor (F1, F2) of sub
PCB (A2P)
NO
The cool/heat unified address
for outdoor units in outdoor -
outdoor unit transmission is
duplicated. Set the address
correctly.
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
NO
YES