Outline of Functions (Outdoor unit)
SiBE811001EB
89
CONVENI-PACK
50
Tc2
45
36
40
38
42
Formula of Tc2 = 1
Formula of Tc2 = 2
Formula of Tc2 = 3
Formula of Tc2 = 4
Formula of Tc2 = 5
Ta
10
20
|
Target Tc
• Target Tc = Min (Target Tc1, Target Tc2)
• Target Tc1: Determined by setting temperature of remote controller
Target Tc1 = Max (Tset) + 20˚C + Tc1 correction (Changeable by service mode, 2 - 29)
Target Tc2: Outdoor air temperature and Tc2 correction (Changeable by service mode, 2 - 32)
OFF (Factory setting)
SET 1
SET 2
SET 3
SET 4
SET 5
Tc1 correction
0˚C
+2˚C
+1˚C
-1˚C
-2˚C
-3˚C
Tc2 correction
(Formula of Tc2)
Formula: 1
Formula: 2
Formula: 3
Formula: 4
Formula: 5