SiBE811001EB
Troubleshooting
CONVENI-PACK
182
Troubleshooting
∗
1. Pull out and insert the connecter once and check it is absolutely connected.
∗
2. Method to check transmission part of indoor unit PCB.
Turn OFF the power and remove the connecter X70A of indoor unit PCB (A1P).
Short-circuit X70A.
After turning ON the power, check below numbers under field setting remote control. (Confirmation:
Second code No. at the condition of first code No. 21 on mode No. 41)
↓
∗
After confirmation, turn OFF the power, take off the short circuit and connect X70A back to original
condition.
Determination
01: Normal
Other than 01: Transmission defect on indoor unit PCB
Connect the connector
accurately.
NO
Replace the indoor unit PCB
(A1P).
NO
Replace the fan PCB (A2P).
YES
Connect it and operate. (It is
possible to have a cause, such
as instantaneous blackout.)
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES
Is the connector
between indoor unit
PCB (A1P) and fan
PCB (A2P)
accurately
connected? (
∗
1)
Under above field
setting mode,
installation position
is "
01
".
Confirm the condition of transmission
on indoor unit PCB using field setting
mode. (
∗
2)
Connect the connecter X70A and turn
on the power again.
"
C1
" Error breaks out
again.