Troubleshooting
SiBE811001EB
267
CONVENI-PACK
8.5.13 Momentary Overcurrent of Inverter Compressor
Error Code
L5
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Error is detected from the current flowing in the power transistor.
Error Decision
Conditions
When an excessive current (36.9A) flows in the power transistor.
Supposed
Causes
Defective compressor coil (Broken wire or insulation failure)
Compressor startup failure (mechanical lock)
Defective inverter PCB
Large differential pressure when compressor startup (0.5 MPa or more)
Instantaneous fluctuations in power supply voltage
LED Indications
First digit
l h k h l l l
Second digit