SiBE811001EB
Troubleshooting
CONVENI-PACK
274
8.5.16 Transmission Error between Inverter and Control PCB
Error Code
LC
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Error Decision
Conditions
When the correct communication is not conducted in certain period
Supposed
Causes
Defective outdoor unit main PCB (transmission section)
External factor (noise etc.)
Defective fan motor
Troubleshooting
LED Indications
First digit
l h k h l l l
Second digit
l k h l l h h
Is the connector for the fan
motor connected to the
outdoor unit main PCB?
Remove the connector for fan motor,
and the operate.
The distance is 50mm
or more.
Check the distance between the
strong electric line and weak electric
line onsite setting.
Keep the distance 50mm or
more.
NO
Properly connect the connector.
NO
Replace the outdoor unit main
PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.