SiBE811001EB
Troubleshooting
CONVENI-PACK
164
8.4.3 Drain Level Control System (S1L) Abnormality
Error Code
A3
Applicable
Models
All indoor models
Method of Error
Detection
By float switch OFF detection
Error Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF
Supposed
Causes
200V power supply is not provided
Defective float switch or short circuit connector
Defective drain pump
Drain clogging, upward slope, etc.
Defective indoor unit PCB
Loose connection of connector