Parameter
Values (Range)
Unit
Step
Default
Description
Trigger mode
1=Single
2=Periodic
3=Continuous
3=Continuous
Specifies the ob-
servation period
triggering mode
Percentile unbal-
ance
1...100
%
1
95
The percent to
which percentile
value PCT_UNB_VAL
is calculated
Obs period selec-
tion
1=1 Hour
2=12 Hours
3=1 Day
4=7 Days
5=User defined
5=User defined
Observation period
for unbalance cal-
culation
User Def Obs peri-
od
1...168
h
1
168
User define obser-
vation period for
statistic calculation
Obs period Str year 2008...2076
2011
Calendar time for
observation period
start year in YYYY
Obs period Str
month
1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
1=January
Calendar time for
observation period
start month
Obs period Str day 1...31
1
Calendar time for
observation period
start day
Obs period Str hour 0...23
h
0
Calendar time for
observation period
start hour
10.4.8
Monitored data
10.4.8.1
VSQVUB Monitored data
Table 724: VSQVUB Monitored data
Name
Type
Values (Range)
Unit
Description
3S_MN_UNB
FLOAT32
0.00...150.00
%
Non sliding 3
second mean val-
ue of voltage un-
balance
10MIN_MN_UNB FLOAT32
0.00...150.00
%
Sliding 10 mi-
nutes mean value
Table continues on the next page
Power quality measurement functions
1MRS758755 C
736
REC615 & RER615
Technical Manual