Parameter
Values (Range)
Unit
Step
Default
Description
Time multiplier
0.05...2.00
0.01
1.00
Time multiplier for
Wattmetric IDMT
curves
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
20=Wattmetric
IDMT
15=IEC Def. Time
Selection of time
delay curve type
Operate delay time 60...200000
ms
10
60
Operate delay time
for definite time
Table 400: WPWDE Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 401: WPWDE Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used cur-
rent measurement
mode
Correction angle
0.0...10.0
deg
0.1
2.0
Angle correction
Min operate current 0.010...1.000
xIn
0.001
0.010
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
Reset delay time
0...60000
ms
1
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used
polarization signal
4.2.6.10
Monitored data
WPWDE Monitored data
Table 402: WPWDE Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
Detected fault
direction
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
387