Parameter
Values (Range)
Unit
Step
Default
Description
2=Non-sliding
TDD alarm limit
1.0...100.0
%
0.1
50.0
TDD alarm limit
Table 703: CMHAI Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial Dmd current 0.10...1.00
xIn
0.01
1.00
Initial demand cur-
rent
10.1.8
Monitored data
10.1.8.1
CMHAI Monitored data
Table 704: CMHAI Monitored data
Name
Type
Values (Range)
Unit
Description
Max demand
TDD IL1
FLOAT32
0.00...500.00
%
Maximum de-
mand TDD for
phase A
Max demand
TDD IL2
FLOAT32
0.00...500.00
%
Maximum de-
mand TDD for
phase B
Max demand
TDD IL3
FLOAT32
0.00...500.00
%
Maximum de-
mand TDD for
phase C
Time max dmd
TDD IL1
Timestamp
Time of maxi-
mum demand
TDD phase A
Time max dmd
TDD IL2
Timestamp
Time of maxi-
mum demand
TDD phase B
Time max dmd
TDD IL3
Timestamp
Time of maxi-
mum demand
TDD phase C
3SMHTDD_A
FLOAT32
0.00...500.00
%
3 second mean
value of TDD for
phase A
DMD_TDD_A
FLOAT32
0.00...500.00
%
Demand value
for TDD for
phase A
3SMHTDD_B
FLOAT32
0.00...500.00
%
3 second mean
value of TDD for
phase B
DMD_TDD_B
FLOAT32
0.00...500.00
%
Demand value
for TDD for
phase B