9.2.8
Monitored data
9.2.8.1
DCSXSWI Monitored data
Table 669: DCSXSWI Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
9.2.8.2
ESSXSWI Monitored data
Table 670: ESSXSWI Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
9.2.9
Technical revision history
Table 671: DCSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
Table 672: ESSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
Control functions
1MRS758755 C
642
REC615 & RER615
Technical Manual