Table 719: Trigger mode observation times
Trigger mode
Observation time
Single
Only one period of observation time is acti-
vated.
Periodic
The time gap between the two trigger sig-
nals is seven days.
Continuous
The next period starts right after the previ-
ous observation period is completed.
The length of the period is determined by the settings
Obs period selection and
User Def Obs period. The
OBS_PR_ACT
output is an indication signal which exhibits
rising edge (TRUE) when the observation period starts and falling edge (FALSE)
when the observation period ends.
If the
Percentile unbalance, Trigger mode or Obs period duration settings change
when
OBS_PR_ACT
is active,
OBS_PR_ACT
deactivates immediately.
1MRS758755 C
Power quality measurement functions
REC615 & RER615
Technical Manual
731