![ABB Relion REC615 Скачать руководство пользователя страница 603](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253603.webp)
PEMMXU Input signals
Table 629: PEMMXU Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
U_A
SIGNAL
0
Phase A voltage
U_B
SIGNAL
0
Phase B voltage
U_C
SIGNAL
0
Phase C voltage
RSTACM
BOOLEAN
0=False
Reset of accumulated
energy reading
8.1.11.4
Settings
PEMMXU Non group settings
Table 630: PEMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Power unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward
Direction of active
power flow: For-
ward, Reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward
Direction of reac-
tive power flow:
Forward, Reverse
Table 631: PEMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Forward Wh Initial
0...999999999
1
0
Preset Initial value for for-
ward active energy
Reverse Wh Initial
0...999999999
1
0
Preset Initial value for re-
verse active energy
Forward VArh Initial
0...999999999
1
0
Preset Initial value for for-
ward reactive energy
Reverse VArh Initial
0...999999999
1
0
Preset Initial value for re-
verse reactive energy
Measurement mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
1=PhsA, PhsB, PhsC
Selected measurement
mode for power calcula-
tion
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
603