Parameter
Values (Range)
Unit
Step
Default
Description
Forward VArh Initial 0...999999999
1
0
Preset Initial value
for forward reactive
energy
Reverse VArh Initial 0...999999999
1
0
Preset Initial value
for reverse reactive
energy
8.1.12.5
Monitored data
Table 638: SPEMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
SL1-kVA:1
FLOAT32
-999999.9...9999
99.9
kVA
Total apparent power,
phase A
SL2-kVA:1
FLOAT32
-999999.9...9999
99.9
kVA
Total apparent power,
phase B
SL3-kVA:1
FLOAT32
-999999.9...9999
99.9
kVA
Total apparent power,
phase C
PL1-kW:1
FLOAT32
-999999.9...9999
99.9
kW
Total active power,
phase A
PL2-kW:1
FLOAT32
-999999.9...9999
99.9
kW
Total active power,
phase B
PL3-kW:1
FLOAT32
-999999.9...9999
99.9
kW
Total active power,
phase C
QL1-kVAr:1
FLOAT32
-999999.9...9999
99.9
kVAr
Total reactive power,
phase A
QL2-kVAr:1
FLOAT32
-999999.9...9999
99.9
kVAr
Total reactive power,
phase B
QL3-kVAr:1
FLOAT32
-999999.9...9999
99.9
kVAr
Total reactive power,
phase C
PFL1:1
FLOAT32
-1.00...1.00
Average power factor,
phase A
PFL2:1
FLOAT32
-1.00...1.00
Average power factor,
phase B
PFL3:1
FLOAT32
-1.00...1.00
Average power factor,
phase C
Table continues on the next page
Measurement functions
1MRS758755 C
608
REC615 & RER615
Technical Manual