Calculation for estimating the remaining life
shows that there are 30,000 possible operations at the rated operating
current of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if the
tripping current is 10 kA, one operation at 10 kA is equivalent to 30,000/60=500
operations at the rated current. It is also assumed that prior to this tripping,
the remaining life of the circuit breaker is 15,000 operations. Therefore, after one
operation of 10 kA, the remaining life of the circuit breaker is 15,000-500=14,500 at
the rated operating current.
Remaining life reduction
=
−
I
I
r
Directional Coef
(Equation 67)
Spring-charged indication
For normal operation of the circuit breaker, the circuit breaker spring should be
charged within a specified time. Therefore, detecting long spring-charging time
indicates that it is time for the circuit breaker maintenance. The last value of the
spring-charging time can be used as a service value.
Gas pressure supervision
The gas pressure supervision monitors the gas pressure inside the arc chamber.
When the pressure becomes too low compared to the required value, the circuit
breaker operations are locked. A binary input is available based on the pressure
levels in the function, and alarms are generated based on these inputs.
7.1.6
Signals
7.1.6.1
SSCBR Input signals
Table 575: SSCBR Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block input status
POSOPEN
BOOLEAN
0=False
Signal for open po-
sition of apparatus
from I/O
POSCLOSE
BOOLEAN
0=False
Signal for close po-
sition of apparatus
from I/O
OPEN_CB_EXE
BOOLEAN
0=False
Signal for open com-
mand to coil
Table continues on the next page
1MRS758755 C
Condition monitoring functions
REC615 & RER615
Technical Manual
563