Parameter
Values (Range)
Unit
Step
Default
Description
(percentage of dif-
ference between
min and max as
0,001 % s)
Ng Seq A Hi high
Lim
0.00...40.00
xIn
1
0.20
High alarm current
limit for negative
sequence current
Ng Seq A High limit 0.00...40.00
xIn
1
0.05
High warning cur-
rent limit for neg-
ative sequence cur-
rent
Ng Seq A low limit
0.00...40.00
xIn
1
0.00
Low warning cur-
rent limit for neg-
ative sequence cur-
rent
Ng Seq A low low
Lim
0.00...40.00
xIn
1
0.00
Low alarm current
limit for negative
sequence current
Ng Seq A deadband 100...100000
1
2500
Deadband configu-
ration value for
negative sequence
current for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Zro A Hi high Lim
0.00...40.00
xIn
1
0.20
High alarm current
limit for zero se-
quence current
Zro A High limit
0.00...40.00
xIn
1
0.05
High warning cur-
rent limit for zero
sequence current
Zro A low limit
0.00...40.00
xIn
1
0.00
Low warning cur-
rent limit for zero
sequence current
Zro A low low Lim
0.00...40.00
xIn
1
0.00
Low alarm current
limit for zero se-
quence current
Zro A deadband
100...100000
1
2500
Deadband configu-
ration value for
zero sequence cur-
rent for integral cal-
culation. (percent-
age of difference
between min and
max as 0,001 % s)
8.1.9.5
Monitored data
CSMSQI Monitored data
Table 622: CSMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
NgSeq-A
FLOAT32
0.00...40.00
xIn
Measured nega-
tive sequence
current
PsSeq-A
FLOAT32
0.00...40.00
xIn
Measured posi-
tive sequence
current
Table continues on the next page
Measurement functions
1MRS758755 C
596
REC615 & RER615
Technical Manual