![ABB Relion REC615 Скачать руководство пользователя страница 216](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253216.webp)
Figure 114: Start value behavior with ENA_MULT input activated
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects
the phase or phases in which the measured current exceeds the setting. If the phase
information matches the
Num of start phases setting, the phase selection logic
activates the timer module.
Timer
Once activated, the timer activates the
START
output. Depending on the value of the
Operating curve type setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value of
Operate delay time in the DT
mode or the maximum value defined by the inverse time curve, the
OPERATE
output
is activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
Curve parameter A, Curve parameter
B, Curve parameter C, Curve parameter D and Curve parameter E.
If a drop-off situation happens, that is, a fault suddenly disappears before the
operate delay is exceeded, the timer reset state is activated. The functionality of
the timer in the reset state depends on the combination of the
Operating curve
type, Type of reset curve and Reset delay time settings. When the DT characteristic
is selected, the reset timer runs until the set
Reset delay time value is exceeded.
When the IDMT curves are selected, the
Type of reset curve setting can be set to
"Immediate", "Def time reset" or "Inverse reset". The reset curve type "Immediate"
causes an immediate reset. With the reset curve type "Def time reset", the reset
time depends on the
Reset delay time setting. With the reset curve type "Inverse
Protection functions
1MRS758755 C
216
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......