Set Mon Act hour = 07 hrs
Set Mon Act Min = 15 min
Set Mon Act Dur = 525 min
Figure 87: Example setting values for Output Q activation
3.17.4.6
Signals
Table 158: DTMGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for bina-
ry output
FREEZE
BOOLEAN
0=False
Freeze signal for bina-
ry output
Table 159: DTMGAPC Output signals
Name
Type
Description
Q
BOOLEAN
Output status
3.17.4.7
Settings
Table 160: DTMGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Monday Act enable
0=False
1=True
false
Activation / deactivation need
on Monday
Monday Act hour
0...23
h
8
Activation hour time for Mon-
day
Monday Act Mn
0...59
min
0
Activation minute time for Mon-
day
Monday off delay
1...1440
min
1
60
Activation duration for Monday
Tuesday Act enable
0=False
1=True
false
Activation / deactivation need
on Tuesday
Tuesday Act hour
0...23
h
8
Activation hour time for Tues-
day
Table continues on the next page
Basic functions
1MRS758755 C
152
REC615 & RER615
Technical Manual