Name
Type
Default
Description
RECL_ON
BOOLEAN
0=False
Level sensitive signal
for allowing (high) /
not allowing (low) re-
closing
SYNC
BOOLEAN
0=False
Synchronizing check
fulfilled
9.4.7.2
DARREC Output signals
Table 687: DARREC Output signals
Name
Type
Description
OPEN_CB
BOOLEAN
Open command for circuit
breaker
CLOSE_CB
BOOLEAN
Close (reclose) command for
circuit breaker
CMD_WAIT
BOOLEAN
Wait for master command
INPRO
BOOLEAN
Reclosing shot in progress,
activated during dead time
LOCKED
BOOLEAN
Signal indicating that AR is
locked out
PROT_CRD
BOOLEAN
A signal for coordination be-
tween the AR and the protec-
tion
UNSUC_RECL
BOOLEAN
Indicates an unsuccessful re-
closing sequence
AR_ON
BOOLEAN
Autoreclosing allowed
READY
BOOLEAN
Indicates that the AR is ready
for a new sequence, i.e. the
CB_READY input equals TRUE
ACTIVE
BOOLEAN
Reclosing sequence is in pro-
gress
9.4.8
Settings
9.4.8.1
DARREC Non group settings
Table 688: DARREC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off/On
Reclosing opera-
tion
1=Off
2=External Ctl
1=Off
Reclosing opera-
tion (Off, External
Ctl / On)
Table continues on the next page
Control functions
1MRS758755 C
684
REC615 & RER615
Technical Manual