Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 359: FDEFLPDEF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Minimum operate
time
50...60000
ms
1
50
Minimum operate
time for IDMT
curves
Allow Non Dir
0=False
1=True
0=False
Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Min operate current 0.005...1.000
xIn
0.001
0.005
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
Correction angle
0.0...10.0
deg
0.1
0.0
Angle correction
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Io signal Sel
1=Measured Io
2=Calculated Uo
1=Measured Io
Selection for used
Io signal
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used
Uo signal
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt.
Reference quantity
used to determine
fault direction
Table 360: DEFHPDEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.10...40.00
xIn
0.01
0.10
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Table continues on the next page
Protection functions
1MRS758755 C
326
REC615 & RER615