Parameter
Values (Range)
Unit
Step
Default
Description
Description
SPCRGAPC1 Output
15
Generic control point description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
-1=Off
Operation mode for generic con-
trol point
Pulse length
10...3600000
ms
10
1000
Pulse length for pulsed operation
mode
Description
SPCRGAPC1 Output
16
Generic control point description
3.17.14
Local generic control points SPCLGAPC
3.17.14.1
Function block
Figure 104: Function block
3.17.14.2
Functionality
The local generic control points function SPCLGAPC is dedicated only for local
controlling, that is, SPCLGAPC cannot be controlled remotely. The local control is
done through the buttons in the front panel.
3.17.14.3
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
SPCLGAPC has the
Operation mode, Pulse length and Description settings available
to control all 16 outputs. By default, the
Operation mode setting is set to "Off". This
disables the controllable signal output. SPCLGAPC also has a general setting
Loc
Rem restriction, which enables or disables the local or remote state functionality.
When the
Operation mode is set to "Toggle", the corresponding output toggles
between "True" and "False" for every input pulse received. The state of the output is
stored in a nonvolatile memory and restored if the protection relay is restarted.
When the
Operation mode is set to "Pulsed", the corresponding output can be used
to produce the predefined length of pulses. Once activated, the output remains
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
183