![ABB Relion REC615 Скачать руководство пользователя страница 545](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253545.webp)
Table 565: MDSOPT Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial value
0...299999
h
1
0
Initial value for op-
eration time super-
vision
Operating time
hour
0...23
h
1
0
Time of day when
alarm and warning
will occur
Operating time
mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate
Operating time
mode for warning
and alarm
6.3.8
Monitored data
6.3.8.1
MDSOPT Monitored data
Table 566: MDSOPT Monitored data
Name
Type
Values (Range)
Unit
Description
MDSOPT
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
OPR_TIME
INT32
0...299999
h
Total operation
time in hours
6.3.9
Technical data
Table 567: MDSOPT Technical data
Description
Value
Motor runtime measurement accuracy
1
±0.5 %
6.3.10
Technical revision history
Table 568: MDSOPT Technical revision history
Technical revision
Change
B
Internal improvement.
C
Internal improvement.
D
Internal improvement.
1
Of the reading, for a stand-alone relay, without time synchronization
1MRS758755 C
Supervision functions
REC615 & RER615
Technical Manual
545
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......