14.9
Double-pole power outputs with TCS function
X100: PO3 and PO4
Table 759: Double-pole power outputs with TCS function X100: PO3 and PO4
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R <40 ms
at 48/110/220 V DC (two contacts connected
in a series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit monitoring (TCS)
• Control voltage range
• Current drain through the monitoring cir-
cuit
• Minimum voltage over the TCS contact
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
14.10
Single-pole power output relays X100: PO1 and PO2
Table 760: Single-pole power output relays X100: PO1 and PO2
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
1MRS758755 C
Technical data
REC615 & RER615
Technical Manual
855