Parameter
Values (Range)
Unit
Step
Default
Description
A high limit
0.00...40.00
xIn
1
1.20
High warning cur-
rent limit
A low limit
0.00...40.00
xIn
1
0.00
Low warning cur-
rent limit
A low low limit
0.00...40.00
xIn
1
0.00
Low alarm current
limit
A deadband
100...100000
1
2500
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 589: CMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
8.1.4.5
Monitored data
CMMXU Monitored data
Table 590: CMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
IL1-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase A
IL2-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase B
IL3-A
FLOAT32
0.00...40.00
xIn
Measured cur-
rent amplitude
phase C
Max demand IL1 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
A
Max demand IL2 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
B
Max demand IL3 FLOAT32
0.00...40.00
xIn
Maximum de-
mand for Phase
C
Min demand IL1
FLOAT32
0.00...40.00
xIn
Minimum de-
mand for Phase
A
Table continues on the next page
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
579