LED indication control is preconfigured in a such way that all the protection
function general start and operate signals are combined with this function
(available as output signals
OUT_START
and
OUT_OPERATE
). These signals are
always internally connected to Start and Trip LEDs. LEDPTRC collects and combines
phase information from different protection functions (available as output signals
OUT_ST_A /_B /_C
and
OUT_OPR_A /_B /_C
). There is also combined earth fault
information collected from all the earth-fault functions available in the relay
configuration (available as output signals
OUT_ST_NEUT
and
OUT_OPR_NEUT
).
3.4
Programmable LEDs
3.4.1
Function block
Figure 13: Function block
3.4.2
Functionality
The programmable LEDs reside on the right side of the display on the LHMI.
1MRS758755 C
Basic functions